Cod Ean8595568932358
Cod vamal85363030
Greutate0.06 kg/pcs
MaterialPP + foaming material
Material fără halogeniyes
Material fără plumbyes
Cu suto-stingere30 sec.
Voltaj nominal<= 400 V
Curent nominal<= 16 A
Rezistența la temperatură-5 - 60 °C
Testat cu buclă incinsă850 °C
Lătime73 mm
Înăltime68 mm
Adâncime47 mm
Diametrul orificiului găurit (forat)73 mm
Recomandările producătorului
For all range of products in hollow walls, we recommend using the milling sets supplied by us.
Clasa de reacție la focA1 - F
Tipuri de protecțieIP30
StandardeČSN EN 60 670-1, ČSN EN 1363-1:2013
Standardele cu privire lade rezistența la focEI 15 - EI 120

Note for system with maintained functionality in fire:
Fire resistant wall box KPZ-1_PO is designed for fire partition walls, consisting of fire resistant gypsum plasterboard or aerated concrete structures. Its advantage is that the inlet openings are made of a softened material that ensures airtightness of the passage between the box and the cable or tube installed therein. On the outside and inside of the box is applied foaming material, which in case of fire foams the mounting hole. This ensures the integrity and insulation fire partitions in place of location devices. Its use thus prevents the spread of fire in the event of fire. The triple-threaded mounting screws are provided with metal feet for quick installation. Application of this box is mainly in buildings with increased need for protection of persons and property in case of fire.

The PO classification is dependent on the specific placement of the box in plasterboard or aerated concrete, detailed in the new catalog – Systems with maintained functionality in fire.